INSTALLATIONS – VEHICLE & MOBILE PLANT
           
Applications
Ideal for vehicles and mobile plant in the mining, logistics, construction and forestry industries, suitable for to all sizes of vehicle and mobile plant.   No pipework, and space and weight saving.
Compliance & Design Issues

The system will be designed to AS 5062. The basis of the calculation will be on GROSS VOLUME of the risk. LEAKAGE AREA will be identified on the design calculation.
There are 3 types of design calculations available – selection will depend on the risk
• AS 5062 – allows additional leakage from Risk • General – limited leakage from Area • Lithium – specific for this Risk type.

Risk Assement required to complay with AS 5062.

Components & System Schematic
FP-08451 – Control Panel
FP-08945 – Panel Cover
FP-08872 – Battery Backup
FP-08860 – Shutdown Module
FP-08850 – Delay Discharge
FP-08879 – Voltage Relay
FP-08825 – Thermal Fuse
FP-14053 – Manual Actuator
FP-14016 – Battery Lead

Areas to Focus
Positioning of FirePro Units Cable Deutsch Plug Connections Accidental Discharge Test Equipment Faults
• Any damage or water ingress will be a fault.

• The Fault LED will light.

• The panel will beep in a coded fashion:
    – 1 beep On Circuit 1 Alarm
    – 2 beeps On Circuit 2 Alarm
    – 3 beeps On Discharge Circuit
    – 4 beeps On Siren Circuit – V4 Panel

• Most faults are incoming power supply
• Panel is 9-30vDC – will fail below 7.5vDC

• Battery Charge at 25v – LED when Charging
• Backup takes over when supply below 25vDC

• Voltage Relay supply drops below 25.6v
   incoming power cut off. Backup battery will
   power system. Relay engages when machine
   battery voltage is above 26.8vDC.

Components to allow for maintenance.
• Locate clear of mechanical-weather.
• FirePro to be secure. Use of HD brackets.
• Minimum safe distances as specified.
• Means of egress or rescue.
Cable install is critical.
• Consider Cable path.
• Use conduit where exposed.
• Cable to be secured with P-Clips.
Deutsch Plug Connections
• Follow pin wiring Diagram.
• Female plugs should be down facing.
• Ensure heatshrink COOLS before locating.
DETECTION CIRCUIT 1
• only way the system can activate.
• Water ingress creating short -> activation.
• Female Plugs installed down facing.
• Cover DPlug connection with HeatShrink.
• Test Module should be connected first.
• Plug directly to panel this isolates all units.
• Runs on 9v Battery.