 |
 |
• Conventional Panel
– Can be used as main Panel – AS7240.
– or CIE where other panel is main.
– If CIE solid door installed.
• Detection available as 2 or 8 zone.
• FirePro Circuits are fully monitored.
• Mimic Panel shows Status of FP Units.
• Activation ISOLATE KEY switch on Panel
• Max 80 FirePro Units per Gas Card
• Use two types of Detection – smoke/heat
– configure for Dual Knock activation.
– dont mix detector types in a single circuit.
• SHUTDOWN of systems required:
– air conditioning.
– power etc particularly in Battery systems.
• Complies to AS 4487 and AS 1670 |
• Uses 484 Bus Communications.
• MAX of 7 Devices using serial comms.
• MAX of 3 Devices from Status Power
• Cannot use 24v AUX power on Gas Module.
• DONT use “T” connections on 485 bus.
• Each Device must have separate address.
• if more than 7 – use mimic connections.
|
|
|
Components to allow for maintenance.
• Locate clear of mechanical-weather.
• FirePro to be secure. Use of HD brackets.
• Minimum safe distances as specified.
• Means of egress or rescue. |
Cable install is critical.
• Consider Cable path.
• Must use screened cable for FirePro Units.
• Use conduit where exposed. |
• Replaces Press.switch “Released” advice.
• Mount to FP unit closets to Panel.
• Fuse is a normally CLOSED Circuit.
• May require setting change on Panel. |
• Test Module should be connected first.
• Plug directly to panel this isolates all units.
• Runs on 9v Battery. |